Model
Dimensions (W*D*H) (mm)
Nominal Capacity
Nominal Voltage
Discharge Ending Voltage
Charging Limited Voltage
Display
Outer Package
Max Charge Current
Max Discharge Current
Weight
Datasheet (PDF)
MC-LFR48-50A
442*388*132
50.0Ah
51.2V
43.2V
57.6V
No
Material White bake
35A
50A
32Kg
Descargar
MC-LFR48-50B
442*388*132
50.0Ah
51.2V
43.2V
57.6V
Yes
Material White bake
10A
50A
31.5Kg
Descargar
MC-LFR48-50C
442*388*132
50.0Ah
51.2V
43.2V
57.6V
Yes
Material White bake
50A
50A
32Kg
Descargar
MC-LFR48-100A
442*388*220
100.0Ah
51.2V
43.2V
57.6V
No
Material White bake
65A
75A
57Kg
Descargar
MC-LFR48-100B
442*388*264
100.0Ah
51.2V
43.2V
57.6V
No
Material White bake
60A
50A
32Kgx2
Descargar
MC-LFR48-150A
442*388*308
150.0Ah
51.2V
43.2V
57.6V
No
Material White bake
50A
60A
83Kg
Descargar
MC-LFR48-200A
600*600*1050
200.0Ah
51.2V
43.2V
57.6V
No
Material White bake
40A
100A
178Kg
Descargar
MC-LFR48-300A
600*600*1250
300.0Ah
51.2V
43.2V
57.6V
No
Material White bake
200A
200A
240Kg
Descargar
Item
Testing method
Requeriment
Performance after of 0.2C discharging
After standard charging, discharge at constant current of 0.2 C10 within 1h till terminal voltage reaches 43.2V, record the discharging time.
Discharge time 300 min
Performance after of 0.5C discharging
After standard charging, discharge at constant current of 0.5 C10 within 1h till terminal voltage reaches 43.2V, record the discharging time.
After standard charging, discharge at constant current of 0.5 C10 within 1h till terminal voltage reaches 43.2V, record the discharging time.
Performance of 0.1C discharging
After standard charging, discharge at constant current time of 0.1 C10 1within 1h till terminal voltage reaches 43.2V, record the discharging time.
Discharge time ≥ 600 min
High temperature performance (60ºC)
After standard charging, put battery pack into high-temperature box of 60 ± 2ºC to keep 4h, then discharge at 1.0 C10 till 43.2V at the same temperature, record the discharging time.
Discharge time ≥ 54 min
Low temperature performance (-10ºC)
After standard charging, put battery pack into high-temperature box of -10 ± 2ºC to keep 6h, then discharge at 0.2 C10 till 43.2V at the same temperature, record the discharging time.
Discharge time ≥ 180 min
Low temperature performance (-20ºC)
After standard charging, put battery pack into high-temperature box of -20 ± 2ºC to keep 6h, then discharge at 0.2 C10 till 43.2V at the same temperature, record the discharging time.
Discharge time ≥ 120 min